PD Doctor Coupler
Three-channel amplifier that boosts the weak signal of partial discharges and prepares it for further processing. This module is responsible for switching ranges, standardizing the signal, or extracting additional MV or HV level information.
Capacitive sensor

The capacitive sensor is designed for connecting PD Doctor components to MV equipment directly on live parts up to 22 kV. It is used to collect the signal of partial discharges as well as the synchronization signal.
Inductive sensor

The inductive sensor is designed for connecting PD Doctor components to non-voltage parts of MV equipment, primarily to the grounding wire of the measured device.
Technical Specifications
Amplifier Parameters
Number of channels | 3 |
Input type | Voltage, current |
Bandwidth | 60 kHz ÷ 1,5 MHz |
Gain | 0 / -12 / -24 / -36 dB |
Synchronization voltage | 15 VAC |
Synchronization frequency | 40 ÷ 70 Hz |
Connector | RJ45 |
Environmental Measurement
Temperature | -40 ÷ +85 °C (±1 °C) |
Humidity | 0 ÷ 100 % (±3 %) |
Pressure | 300 ÷ 1100 hPa (±1,7 hPa) |
Mounting
Mounting | On the wall |
Enclosure | Molex 936040024 |
IP rating | IP65 |
Environment
Operating temperature | -40 to +60 °C |
Storage temperature | -40 to +70 °C |
Humidity Non-condensing | 0 – 80 % |
Power supply
Voltage | 12 VDC |
Maximum current | 0,15 A |
Dimensions and weight
Dimension | 165 x 195 x 65 mm (D x W x H) |
Weight | 0,8 kg |